ABB Drives ACS355 IP66 Sensorless Flux Vector AC Frequency Inverter for 0.75kW (1HP) 400V 3 Ph motor in VxF or Vector control to 2.4A. Simple to set-up for a standard AC Induction motor.
IP66 / UL Type 4X protection for the harshest and most demanding of conditions. See linked products below for compatible options and standard (IP20) equivalent.
R1 Size – 195mm Wide x 281mm Deep x 305mm high. IP66 case.
Overload – 150% x 60seconds.
Speed Control Range – 0/500Hz.
Braking at full load for 60 seconds every 120 seconds to 165 Ohm minimum, 590 Ohm Maximum external resistor (not supplied) – see the Resistor options linked below or use the ‘Which Resistor’ button on this page.
Features – Assistant Operator Panel (Advanced Keypad), 2 x Analogue Inputs, 5 x Digital Inputs, 1 x Analogue Output, 1 x Digital Output, 1 x Relay Contact set.
DC Bus terminals with charge limit in circuit for DC supply or common bus energy saving applications.
‘Safe Torque Off’ function to SIL 3.
Programmable from a PC via ‘DriveWindow’ or using the ABB FlashDrop tool.
Input Current – 4.1A.
Input Voltage – 380-480V three phase at 48-63Hz.
EMC Fliters to IEC/EN 61800-3 2nd Environment C3 (Industrial).
Rated at 40C Ambient.
Ventilation space above and below – 75mm.
Ventilation space at sides – Ensure that there is enough free space around the drive to clean it.
Heat Loss at max output – 49.7W.
Wall Mounting using 4 x screw fixings at rear. Use spacers and fastening lugs to provide clearance for cleaning.
Full part number is – ACS355-03E-02A4-4+B063 (3AUA0000058158) and is a direct replacement for the equivalent ACS350.