0865 735 110

The floor-mounted battery automatic charger is charged with 20Amp and float charge CH1812 / CH1824 KUTAI

specification
AC input
Voltage 110 / 220 Vac +/-10% single phase (jumper selectable)
Frequency 50/60 Hz +/-5%
Uniform charge output voltage
The CH1812 is 14.5 Vdc when charging a 12 Vdc battery
The CH1824 is 28.8 Vdc when charging a 24 Vdc battery
Float output voltage
The CH1812 is 13.8 Vdc when charging a 12 Vdc battery
The CH1824 is 27.6 Vdc when charging a 24 Vdc battery
Uniform charge voltage adjustment range
12 Vdc 13.5 – 16.0 Vdc
24 Vdc 27.0 – 31.0 Vdc
Float voltage adjustment range
12 Vdc 13.0 – 14.5 Vdc
24 Vdc 25.8 – 28.0 Vdc
Protection features
Constant voltage, current limiting, short-circuit protection, surge suppression characteristics, reverse current choke circuit
Rated output current
0.5 – 20.0 Adc
DC voltage rate of change
Less than +/-1%
Average charge charging time
It can be set for 6, 12 or 24 hours
Charging method
Equalization Charge/Float Charge
Cooling method
Fan cooling
efficiency
>80% at full load
Ripple rate
+/-3%
Appearance panel configuration
DC voltmeter
DC ammeter
Power indicator
Charge the indicator light
Float indicator
Charge the setting button
Uniform charge voltage adjustment
Float charge voltage adjustment
Charge current adjustment
Enter the power MCCB
Output power MCCB
Positive Output Terminal (+) / Negative Terminal (-)
Working environment
as temperature
-20 to +60 °C
Storage temperature
-20 to +40 °C
Relative turbidity
Below 90%.
Physical characteristics
size
315.0 (L) x 253.0 (W) x 233.0 (H) mm
weight
CH1812 15.6 Kg +/-2%
CH1824 21.0 Kg +/-2%

.
.
.
.